| Powerware 9120 |
| Rating |
700 VA |
1000 VA |
1500 VA |
2000 VA |
3000 VA |
5000 VA |
6000 VA |
| Part number |
05147361 -5501 |
05147362 -5501 |
05147363 -5501 |
05147364 -5501 |
05147365 -5501 |
1018289 |
1018290 |
| Capacity (VA/watts) |
700/ 490 |
1000/ 700 |
1500/ 1050 |
2000/ 1400 |
3000/ 2100 |
5000/ 3500 |
6000/ 4200 |
| Dimensions WxDxH (mm) |
155x410x240 |
170x445x275 |
215x470x365 |
280x580x570 |
| Weight (kg) |
13 |
15 |
20 |
37 |
38 |
91 |
Input connection |
IEC320/10A |
IEC320/16A |
Hardwired |
| Output connection |
4xIEC320/10A |
1xIEC320/16A 4xIEC320/10A |
Hardwired |
Typical runtime Full
load |
8 min |
8 min |
7 min |
14
min |
8 min |
10 min |
8
min |
Typical runtime Half load |
20 min |
21 min |
20 min |
30 min |
20 min |
22 min |
20 min |
| Operational |
| Nominal input voltage (Vac) |
220/230/240
Vac |
Input voltage range |
120/140/160-276 Vac(700-3000
VA) 120/140/184-276 Vac (5000-6000 VA) |
| Operating frequency |
50/60 Hz auto
sensing (+/-3 Hz, adjustable) |
|
Input power
factor |
>0,97 (700-3000 VA) >0,99 (5000-6000
VA) |
Nominal output voltage |
208/220/230/240
VAC |
Output voltage regulation |
+/-2% online; +/-3% on battery mode |
| Overload capacity |
Up to 125 % for
1 minute, 125-150% for 10 sec |
|
Efficiency |
>86% 700 VA; >88% 1000-3000 VA; >90%
5000-6000 VA (Online mode) >90% 700 VA; >93%
1000-3000 VA; >95% 5000-6000 VA (High efficiency
mode) |
| User interface |
|
LCD display |
LCD display showing both UPS meters and UPS
settings |
| LED |
Four LEDs; UPS
On, UPS on Battery, UPS on bypass, Alarm |
|
Standard communication
ports |
RS232 and USB as standard on all models |
| Optional |
Connectivity
slot for SNMP/WEB card and relay card |
| Environmental |
|
Operating
Temperature |
0°C to +40°C |
| Storage Temp |
-15°C to
+40°C |
|
Altitude |
< 3000 M |
| Audible Noise |
< 45
dB (700-1500 VA) |
<50
dB (2000-3000 VA) |
<55
dB (5000-6000 VA) |
| Certification |
|
Markings |
CE/GS/UL (700-2000 VA) |
CE/GS (3000VA-6000 VA) |
| Safety |
EN 50091-1-1 & UL
1778 (700-2000 VA) |
EN50091-1-1 (3000-6000
VA) |
|
EMC |
EN 50091-2, EN6100-3-2 (700-3000 VA) |