Powerware 5125 |
| Rating |
1000 VA |
1500 VA |
2200 VA |
| Part number |
05146630-5501 |
05146633-5501 |
05146637-5501 |
| Capacity (VA/watts) |
1000/700 |
1500/1050 |
2200/1600 |
| Dimensions WxDxH (mm) |
162x401x250 |
162x467x250 |
162x467x250 |
| Weight (kg) |
16 |
23 |
31 |
| Input connection |
IEC320/ 10A |
| Output connection |
6xIEC320 10A |
9xIEC320 10A |
| Typical runtime (Full load) pf
0,9 |
5 min |
6 min |
6
min |
| Operational |
| Nominal input voltage (Vac) |
220/230/240
Vac |
|
Input voltage
range |
166-276 VAC (+20/-30% of nominal) |
| Operating frequency |
50/60 Hz auto
sensing |
|
Input power
factor |
Same as load |
| Nominal output voltage |
220/230/240
Vac |
|
Output voltage
regulation |
-10%/+6% of selected nominal voltage |
| Overload capacity |
110% 3 min;
150% 10 cycles |
|
Efficiency |
95% |
|
User
interface |
| LED |
Informative
LED display |
|
Standard communication
ports |
RS232 |
| Optional |
SNMP/WEB
card, USB card |
| Environmental |
|
Operating
Temperature |
0°C to +40°C |
| Storage Temp |
-15°C to
+55°C |
|
Altitude |
< 3000 m |
| Audible Noise at 1 metre |
< 45
dB normal mode <50 dB battery mode |
| Certification |
|
Markings |
CE/GS/UL |
| Safety |
EN 50091-1-1 & UL
1778 |
|
EMC |
EN 50091-2, EN6100-3-2 |
Powerware 5125 Battery Run Time
Chart (in minutes)
|
Load VA/W |
1000 VA |
1500 VA |
2200 VA |
| 250/175 |
30 (180) |
60 (240) |
100 (360) |
| 500/350 |
15 (100) |
35 (150) |
60 (180) |
| 750/525 |
10 (60) |
20 (100)
|
45 (115) |
| 1000/700
|
5 (48) |
13 (60) |
28 (75) |
| 1250/875 |
|
8 (40) |
19 (55) |
| 1500/1050
|
|
6 (30) |
15 (40) |
| 1750/1225 |
|
|
12 (35) |
| 2000/1400
|
|
|
10 (30) |
| 2200/1600 |
|
|
6 (28) |
* In the interest of continual product improvement all
specifications are subject to change without notice.
|